venerdì 4 ottobre 2013

TP170B E WinccFlexible 2008

IN CASO SI PASSI DA PROTOOL A WINCCFLEXIBLE 2008 SU PANNELLO TP170B MONO E AL PRIMO
TRASFERIMENTO VI VIENE CHIESTO DI AGGIORNARE IL SISTEMA OPERATIVO, FATELO!!

UNA VOLTA AGGIORNATO IL SISTEMA OPERATIVO TRASFERITE NUOVAMENTE IL PROGETTO.
IN CASO VI VENGA SEGNALATO UN ERRORE (CONTROLLATE L'INTERFACCIA E I CAVI ECC.) DOVETE ENTRARE NEL PANNELLO
PREMENDO CANCEL NELLA FINESTRA IN CUI VI E' SCRITTO CONNECTING HOST. TRA I TRE TASTI PROPOSTI ANDATE SU CONTROL PANEL.

DOPO DI CHE ANDATE SU TRANSFER (PER TROVARLO DOVRETE SCORRERE LA SCROLLBAR DI DESTRA IN CASO IL PANNELLO SIA UN 6 POLLICI) ,
NELLA LINGUETTA CHANNEL TOGLIETE LA SPUNTA IN ENABLE CHANNEL RS232 E METTETELA SU MPI/PROFIBUS CON ANCHE REMOTE CONTROL.

FATTO QUESTO, TRASFERITE NUOVAMENTE IL PRGETTO E TUTTO DOVREBBE ANDARE A BUON FINE.

Nessun commento:

Posta un commento